Every year, before the first freeze, the ritual of irrigation “blow out” becomes the priority for all
irrigation systems that are in regions of the country where the frost level extends below the depth of
the installed piping.
Even if you have drained some water out of the system, the remaining water can freeze, expand and
crack the PVC piping (rigid, white pipe), usually from fitting to fitting. Polyethylene pipe (Flexible,
black pipe) is used in many freezing climates. Although polyethylene pipe is more flexible and can
expand under pressure, water left inside could still freeze and rupture the pipe walls. Freezing water in
the Backflow Assembly will damage the internal components and could possibly crack the brass body.
To minimize the risk of freeze damage to your irrigation system, you’ll need to “winterize” your
irrigation system.
Irrigation systems in areas where “winterization” is mandatory are installed using one of three types
of water removal in mind: manual drain, auto drain, or blowout. If you don’t know your system type,
it would be best to use the blowout method.
Manual Drain Method. Use when manual valves are located at the end and low points of the
irrigation piping. To drain these systems, simply shut off the irrigation water supply (shut off will be
located in the basement and will be either a gate/globe valve(1), ball valve(2) or stop & waste valve(3))
and open all the manual drain valves. Once the water has drained out of the mainline, open the boiler
drain valve(4) or the drain cap on the stop & waste valve (whichever is used in your area) and drain
all the remaining water that is between the irrigation water shut off valve and the backflow device.
Open the test cocks on the backflow device. If your sprinklers have check valves you’ll need to pull
up on the sprinklers to allow the water to drain out the bottom of the sprinkler body. Depending on
the location of the drain valves, there could be some water left in the backflow, the piping and the
sprinklers. When all the water has drained out, close all the manual drain valves.
Automatic Drain Method. Use when automatic drain valves are located at the end and low points
of the irrigation piping. These will automatically open and drain water if the pressure in the piping is
less than 10 PSI. To activate these, you simply shut off the irrigation water supply (shut off will be
located in the basement and will be either a gate/globe valve(1), ball valve(2) or stop & waste valve(3)) and activate
a station or zone to relieve the system pressure. Once the water has drained out of the mainline, open the
boiler drain valve(4) or the drain cap on the stop & waste valve (whichever is used in your area) and
drain the remaining water that is between the irrigation water shut off valve and the backflow device.
Open the test cocks on the backflow device. If your sprinklers have check valves you’ll need to pull
up on the sprinklers to allow the water to drain out the bottom of the sprinkler body. Depending on
the location of the drain valves, there could be some water left in the backflow, the piping and in the
sprinklers.
In some areas you might have a combination of the manual drain system on the mainline (the pipe
between the irrigation water shut off valve and the valves) and auto drain system on the lateral lines
(the pipe between the valves and the sprinklers).
“Blow Out” Method. It is recommended that a qualified licensed contractor perform this type
of “Winterization” method. The blow out method utilizes an air compressor with a Cubic Foot per
Minute (CFM) rating of 80-100 for any mainline of 2" or less. These types of compressors can be
rented at your local equipment rental yard. The compressor is attached to the mainline via a quick
coupler, hose bib or other type connection, which is located after the backflow device. Compressed
air should not be blown through any backflow device. To start the “blow out”, shut off the irrigation
water supply and, with the compressor valve in the closed position, attach the air compressor hose to
the fitting. Activate the station on the controller that is the zone or sprinklers highest in elevation and
the furthest from the compressor. Close the backflow isolation valves. Then slowly open the valve on
the compressor; this should gradually introduce air into the irrigation system. The blow out pressure
should remain below the maximum operating pressure specification of the lowest pressure rated
component on that zone and should NEVER exceed 80 PSI.
Each station/zone should be activated on the controller starting from the furthest station/zone from the compressor
slowly working your way to the closest station/zone to the compressor. Each station/zone should be
activated until no water can be seen exiting the sprinkler heads, this should take approximately two minutes
or more per station/zone. It is better to use two or three short cycles per station/zone than to have
one long cycle. Once the station/zone is dry, you should not continue to blow air through the pipe.
Compressed air moving through dry pipes can cause friction, which will create heat and the heat
could cause damage.
Additional Steps:
Once the water has been removed from the irrigation system, disconnect the air compressor and
release any air pressure that may be present. If your backflow device, the most common backflow
installed is called a Pressure Vacuum Breaker, has ball valves, open and close the isolation valves
on the backflow device numerous times to ensure that any trapped water has escaped from the
upper areas. Leave the isolation valves open at a 45˚ angle (approximately ½ open) and open the
test cocks.
Types of Valves: